48 VNOM Blue Ion energy storage system is designed to be compatible
with the majority of charge controllers and inverters that work with
traditional lead acid batteries.
By
setting the bulk, absorb, float, and equalize set points to these
values, we are overriding the logic of the chargers to allow the full
power of the charging source to be applied to the Battery Management
Unit. In this way, the Battery Management Unit is monitoring each
battery module for current, temperature, and voltage precisely balancing
each cell in every module. When the battery modules have reached the
recommended highest voltage of 55.2 VDC and an associated 100% State of
Charge, the programming of the charging set points simply turns the
charging source off or maintaining a float voltage.
The
inverter settings in this application note are meant to better match
the performance of the Blue Ion Energy Storage System to the
capabilities of the Sol-Ark inverters and maximize the usable system
performance. Each project has its own variables that must be accounted
for when setting inverter parameters. Carefully review these settings,
they can be changed to optimize the performance of your particular
system.